If cutting is performed on external face, seals are installed to prevent any infiltration. These seals are composed of a category 1 SNJF sealant, low modulus elastic, on joint. The width of the seals (ej) must comply with the following minimum dimensions (factor 4 takes account of the fact that seal deformation must be limited to 1/4 of its thickness).
ej ≥ 4.10-5 x ΔT x Lmax
Where ΔT = max (50-T0 ; T0 30); T0 : application temperature
In the event of seismic loading, the thickness of any seals could be increased as a function of the structure design.



Horizontal seal on outer skin:
If outer joinery and woodwork is included in the design, a method of draining any infiltration water is installed in its upper part.
Illustration of upper cross beam in outer joinery and woodwork:

Illustration of upper cross beam in outer joinery and woodwork - roller shutter:

Illustration of upper cross beam in outer joinery and woodwork: with sub-frame:

Any provisions for installing external windows or doors in GBE walls must comply with the provisions set out in NF DTU 36-5 P1-1 and P1-2. The joinery and woodwork must be fixed on the internal face and must be designed so that it does not touch the expandable outer skin. A continuous watertight seal must be installed between the door frames and the concrete faces.

Weather-exposed wall heads are protected against water infiltrations by a cap (on the top of the acroterion) that covers the entire thickness of the wall, attached to the structural internal face only. A small layer of non-reinforced concrete can be applied to the insulation section to protect it during the preliminary phase (i.e. pending the installation of the cap).
Protection of wall head with open height and aluminium cap/Protection of wall head with fully closed height and aluminium cap:


Watertightness complex solutions for nearly flat roofs: (* dimensions to be defined in accordance with the DTU (French codes of practice in the building industry) and thermal coefficient).